Electrical Engineering

Cable Sizing by Voltage Drop: Pick the Right Conductor Every Time

Advertisement

Sizing cable is not just about current rating — voltage drop often dictates a bigger conductor than ampacity alone would suggest, especially on long feeders.

This guide shows the voltage-drop sizing method and how to apply derating.

Minimum copper area vs allowed drop (50 m, 30 A) 8.75 mm²6 V6.56 mm²8 V5.25 mm²10 V4.38 mm²12 V3.5 mm²15 V
Minimum copper area vs allowed drop (50 m, 30 A)

The formula

A = (2 × L × I × ρ) ÷ Vd_max — solve for the minimum cross-section that keeps drop within budget, then round up.

Worked example

For 50 m at 30 A with a 10 V budget: A = (2 × 50 × 30 × 0.0175)/10 = 5.25 mm² → choose the next standard size, 6 mm².

Don't forget derating

Apply temperature and grouping factors from IEC 60364 or the NEC after the voltage-drop check.

Related calculators

Frequently asked questions

Ampacity or voltage drop first?

Check both — pick whichever demands the larger conductor, then derate.

Why round up?

Standard cable sizes are discrete; rounding up guarantees you stay within the drop budget.

This guide is for educational purposes. Always verify against the relevant standard before final design.

Advertisement

More articles